Normal service conditions of switchgear as follows: | |
Ambient temperature: | |
Maximum | +40°C |
Maximum 24 hour average | +35°C |
Minimum (according to minus 15 indoor classes) | -10°C |
Ambient humidity: | |
Daily average relative humidity | less than 95% |
Monthly average relative humidity | less than 90% |
Earthquake intensity | less than 8 degree |
Height above sea level | less than 1000m |
Saturated vapor pressure: | |
average pressure of a day | should be no more than2. 2kPa |
the average pressure of a month | should be no more than 1.8kPa |
This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.
NO | Item | Units | Technical parameters | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated short-duration power frequency withstand voltage |
| 42/48(Interphase, ground/fracture) | ||
3 | Rated lightning impulse withstand voltage |
| 42/48(Interphase, ground/fracture) | ||
4 | Rated frequency | Hz | 50 | ||
5 | Rated current | A | 630 1250 | 630 1250 1600 | 630 1250 1600 |
6 | Rated short-circuit breaking current | KA | 20/25 | 31.5 | 40 |
7 | Rated short-time withstand voltage |
| 20/25 | 31.5 | 40 |
8 | Rated short circuit duration | S | 4 | ||
9 | Rated peak withstand current | KA | 50/63 | 80 | 100 |
10 | Rated short circuit closing current |
| 50/63 | 80 | 100 |
11 | Secondary circuit power frequency withstand voltage (1min) |
| 2000 | ||
12 | Rated single / back to back capacitor group breaking current | A | 630/400(40kA:800/400) | ||
13 | Rated capacitor bank closing current |
| 12.5 (frequency is not greater than) | ||
14 | Mechanical life | KA | 20000 | ||
15 | Rated current breaking times (electrical life) |
| 20000 | ||
16 | Rated short circuit current breaking times | times | 50(40KA≤30) | ||
17 | Dynamic and static contacts allow wear cumulative thickness | mm | 3 | ||
18 | Energy storage time | s | ≤10 | ||
19 | Contact opening distance | mm | 11±1 | ||
20 | Overtravel |
| 3.5±0.5 | ||
21 | Contact closing bounce time | ms | ≤2(40KA≤3) | ||
22 | Three-phase split/closed period |
| ≤2 | ||
23 | Average opening speed (contacts are separated by -8mm) | m/s | 1.2±0.2 | ||
24 | Main conductive loop resistance |
| 0.6±0.2 | ||
25 | Main conductive loop | μΩ | ≤50(630A)≤45(1250A) | ||
26 | Rated operation sequence |
| 0-0.3s-Co-180s-Co | ||